The running cost of a heat pump depends on a ratio: how much heat it delivers for each kWh of electricity. There are three ways of expressing it, and they are not interchangeable.
Three numbers
- COP: the heat output divided by the electrical power input, under defined test conditions: for an air-to-water heat pump, outdoor air at 7 °C and water leaving at 35 °C or 55 °C [76]. It describes a moment, not a year.
- SCOP: the coefficient of performance over a reference heating season, with the average European climate: the reference annual heating demand divided by the annual energy consumption [76]. It applies to one water outlet temperature, 35 °C (low temperature) or 55 °C (medium temperature) [76]. It is the data sheet figure and is used to compare different models under the same conditions.
- JAZ (Jahresarbeitszahl): the heat produced divided by the electricity used over a year of operation, in a real house [7]. It is only known afterwards, from the meters.
The calculator asks for the JAZ because the cost of a year depends on real operation. If you only have the SCOP from the data sheet, you can use it as a first value and check in the table what changes with lower values.
What has been measured
| Study | Systems | Annual performance factor measured |
|---|---|---|
| Fraunhofer ISE, existing houses in Germany, completed in 2025 | 61 air-to-water | average 3.4; from 2.6 to 4.9 |
| Fraunhofer ISE, same project | 16 ground-source | average 4.3; from 3.6 to 5.4 |
| Fraunhofer ISE, earlier project completed in 2019 | air-to-water | average 3.1 |
| Electrification of Heat, United Kingdom | 428 air-to-water | average about 2.8 |
Sources: Fraunhofer ISE [7], OpenEnergyMonitor on the Electrification of Heat trial [11]. Fraunhofer ISE found no relationship between the year the houses were built and efficiency, and in its air-to-water systems the electric backup heaters accounted for 1.3% of the electricity [7].
How much the JAZ affects the cost
For a house that burns 20,000 kWh of gas with a 90% boiler, with gas at 11.93 ct/kWh and electricity at 37 ct/kWh, the 2026 BDEW averages [9] [8], without standing charges:
| JAZ | Electricity in a year | Cost with the heat pump | Compared with gas (€2,386) |
|---|---|---|---|
| 2.6 | 6,923 kWh | €2,562 | €176 more |
| 3.1 | 5,806 kWh | €2,148 | €238 less |
| 3.4 | 5,294 kWh | €1,959 | €427 less |
| 4.0 | 4,500 kWh | €1,665 | €721 less |
| 4.9 | 3,673 kWh | €1,359 | €1,027 less |
At these prices the two costs break even at a JAZ of about 2.8. Between the lowest and the highest values measured by Fraunhofer ISE in air-to-water systems, the difference is about €1,200 a year. Open this case in the calculator.
Sources
- Wärmepumpen heizen auch im Altbau klimafreundlich: Forschungsprojekt abgeschlossen (comunicato stampa, 3 novembre 2025) · Fraunhofer ISE, retrieved 13 Oct 2026
- BDEW-Strompreisanalyse Herbst 2026 · BDEW Bundesverband der Energie- und Wasserwirtschaft, retrieved 13 Oct 2026
- BDEW-Gaspreisanalyse August 2026 · BDEW Bundesverband der Energie- und Wasserwirtschaft, retrieved 13 Oct 2026
- Electrification of Heat: analisi dei dati di monitoraggio · OpenEnergyMonitor, retrieved 13 Oct 2026
- Regolamento (UE) n. 813/2013 della Commissione, progettazione ecocompatibile degli apparecchi per il riscaldamento d’ambiente, allegato I · Unione europea, EUR-Lex, retrieved 15 Oct 2026