Usable capacity, nominal capacity and efficiency of a battery
Updated 16 Oct 2026 · KilowattTally · Facts checked on
Two “8 kWh” batteries can deliver different amounts of energy to the house, as HTW Berlin’s examples below show [6]. Before entering a capacity in the calculator, it helps to know which data sheet figure you are reading.
Nominal and usable
- Nominal capacity: the energy stored in the cells [6]. Not all of it can be used: reserves for ageing and for safety, and protection against deep discharge, reduce it [6].
- Usable capacity (in German nutzbare Speicherkapazität): the energy that can be drawn during discharge [6]. This is the figure to compare and to enter in the calculator.
- Depth of discharge: the ratio between usable and nominal [6]. A battery used between 5% and 95% state of charge has a depth of discharge of 90% [6].
HTW Berlin, in the Stromspeicher-Inspektion 2026, gives two examples [6]. One data sheet states 16 kWh and a depth of discharge of 90%: the usable capacity is 14.4 kWh. For a BYD HVS+ 7.7, the battery manufacturer declares 7.7 kWh usable with 100% depth of discharge, but the inverter manufacturer limits it to 95% and declares 7.3 kWh; in the laboratory HTW measured 7.4.
How far data sheets differ from measurements
Of 12 systems tested, 11 state the usable capacity on the battery data sheet [6]. The usable capacity measured in the laboratory differed from the data sheet by −7 to +8 percentage points, and for 7 of the 12 systems the measurement was higher than the data sheet [6]. The measured usable capacities ranged from 6.4 to 7.6 kWh for four smaller systems and were above 11.9 kWh for five systems [6].
Efficiency
The energy that comes back from the battery is less than the energy that goes in. HTW measures the efficiency of the battery itself, including the battery’s charging and discharging losses, and that of the electronics on each path of the energy [6]. The efficiency of a path is the average of the values measured at 10 power levels between 5% and 95% of the nominal power [6].
HTW estimates a full round trip by multiplying the average efficiencies of charging, battery and discharging [6]. We did this for each of the 12 systems, with HTW’s codes. Charging is from photovoltaics for the DC-coupled systems and from the AC side for the three AC-coupled systems [6]:
| System | Coupling | Charging | Battery | Discharging to the house | Round trip (our calculation) |
|---|---|---|---|---|---|
| A1 | AC | 97.4% | 95.8% | 97.7% | 91.2% |
| B1 | AC | 94.8% | 95.2% | 95.1% | 85.8% |
| B2 | AC | 96.8% | 96.0% | 96.9% | 90.0% |
| B3 | DC | 96.1% | 95.2% | 95.1% | 87.0% |
| B4 | DC | 98.2% | 96.0% | 96.9% | 91.3% |
| C1 | DC | 96.1% | 94.8% | 96.2% | 87.6% |
| D1 | DC | 97.9% | 95.1% | 97.0% | 90.3% |
| E1 | DC | 97.6% | 97.1% | 97.6% | 92.5% |
| F1 | DC | 98.1% | 96.0% | 97.8% | 92.1% |
| G1 | DC | 97.4% | 95.7% | 96.8% | 90.2% |
| H1 | DC | 92.0% | 95.2% | 91.2% | 79.9% |
| I1 | DC | 95.0% | 87.9% | 95.6% | 79.8% |
The round trip ranges from about 80% to 92.5%. The median of the 12 systems is 90.1%: the calculator uses 90% for the whole round trip, charging and discharging together. For a battery charged from the grid, in the dynamic tariff calculator, only the 10 systems for which HTW reports charging from the AC side count [6]: the median is 89.9%, and there too we use 90%. HTW points out that batteries usually discharge at low power, where the inverter’s efficiency drops sharply [6]: the path averages do not show this, so the round trip of a real battery can be lower.
How much they affect self-sufficiency
We repeated the calculation for a house using 4,500 kWh in a year with 6 kWp facing south, with the BDEW load profile [1] and the PVGIS weather year [4], changing only the round-trip efficiency, with a battery of 6 kWh usable:
| Round-trip efficiency | Self-sufficiency | From the grid in a year |
|---|---|---|
| 80% | 65.5% | 1,553 kWh |
| 85% | 66.2% | 1,521 kWh |
| 90% | 66.9% | 1,491 kWh |
| 95% | 67.5% | 1,464 kWh |
For this house, 15 points of efficiency are worth 2 points of self-sufficiency, while in the same simulation going from 6 to 8 kWh usable is worth about 3, and going from 0 to 6 kWh about 30 (open the calculation). For this house, then, usable capacity weighs more than efficiency, which still counts towards the kWh over a year: with 80% instead of 90% and a 6 kWh battery, self-sufficiency falls by about 1.4 points. Standby consumption, which HTW measures for each system [6], is not counted here.
Sources
- Repräsentative Profile BDEW H25, G25, L25, P25, S25 (Veröffentlichung) · BDEW Bundesverband der Energie- und Wasserwirtschaft, retrieved 13 Oct 2026
- PVGIS 5.3, serie orarie (seriescalc), banca dati PVGIS-SARAH3 · Commissione europea, Joint Research Centre (JRC), retrieved 13 Oct 2026
- Stromspeicher-Inspektion 2026 · HTW Berlin e aquu, retrieved 13 Oct 2026